improve your lifeApril 2008Improve your lifeMINI MULTISET V.R.F. DC INVERTER R410ATECHNICAL DATAOUTDOOR UNITS
22 - 3Design of Mini Multiset1. Model Selecting and Capacity Calculator1-2. Procedure for Selecting Models and Calculating Capacity Model Selection
22 - 4Design of Mini Multiset1. Model Selecting and Capacity Calculator1-3. Calculation of Actual Capacity of Indoor Unit Calculating the actual ca
22 - 5Design of Mini Multiset1. Model Selecting and Capacity Calculator<Heating>● Outdoor unit corrected heating capacity (5) = Outdoor unit ra
22 - 6Design of Mini Multiset1. Model Selecting and Capacity CalculatorRefer to the graph below for the correction coefficients for Ruc and Ruh.Indoo
22 - 7Design of Mini Multiset1. Model Selecting and Capacity Calculator Outdoor unit heating capacity correction coefficient during frosting/defrost
22 - 8Design of Mini Multiset1. Model Selecting and Capacity Calculator Graph of indoor unit capacity characteristics (2 – (1)) Graph of capacity c
22 - 9Design of Mini Multiset1. Model Selecting and Capacity Calculator1-4. Capacity Correction Graph According to Temperature Condition Capacity c
22 - 10Design of Mini MultisetFor model combinations (inverter model + constant-speed model) of 22 HP or higher, the lower limit for the out-door air
22 - 11Design of Mini Multiset1. Model Selecting and Capacity Calculator1-5. Capacity Correction Graph According to Tubing Length and Elevation Diff
22 - 12Design of Mini Multiset1. Model Selecting and Capacity CalculatorTable 1 Correction coefficient for equivalent length when the size of the ga
ASAWS/AWFACSADPSAFSAFNSAESIndoor Unit T ype 22 283656 641061 40AS1S**1-W ay Air Discharge AS1S22MH AS1S28MH AS1S36MHSemi-ConcealedASBS**1-W ay Air Dis
22 - 13Design of Mini Multiset2. System Design2-1. Tools Required for Installation (not supplied)1. Standard screwdriver2. Phillips head screwdriver3
22 - 14Design of Mini Multiset2. System DesignMaterial OCopper tubingOuter diameter 6.35 9.52 12.7 15.88Wall thickness 0.8 0.8 0.8 1.0 1.019.05Table 2
22 - 15Design of Mini Multiset2. System Design2-7. Additional Refrigerant ChargeAdditional refrigerant charge amount is calculated from the liquid tu
22 - 16Design of Mini Multiset2. System DesignMinimum indoor volume & floor area as against theamount of refrigerant is roughly as given in the fo
22 - 17Design of Mini Multiset2-11. System Example(1) Below are the tables created using the “Sanyo PAC/GHP System Diagram Software.” Details of the
22 - 18Design of Mini MultisetOutdoor unitRoom 1(indoor unit 1)Room 2(indoor unit 2)Room 3(indoor unit 3)Room 4(indoor unit 4)Selected model AES 06 MM
22 - 19Design of Mini Multiset2. System Design2-12. Example of Tubing Size Selection and Refrigerant Charge AmountAdditional refrigerant chargingBase
22 - 20Design of Mini Multiset2. System DesignChecking of limit density Density limit is determined on the basis of the size of aroom using an indoor
22 - 21Design of Mini Multiset2. System Design2-13. Installing Distribution Joint(1) Refer to “HOW TO ATTACH DISTRIBUTIONJOINT” enclosed with the opt
22 - 22Design of Mini MultisetDDVI 16Use: For indoor unit (Capacity after distribution joint is 22.4 kW or less.)Table 2-12 Dimension for Connections
iIMPORTANT! Please Read Before StartingThis air conditioning system meets strict safety and operat-ing standards. As the installer or service person,
22 - 23Design of Mini Multiset2. System DesignBall Valve Installation (for refrigerant R410A only)Check the size of the ball valve set you separately
22 - 24Design of Mini Multiset2. System Design2-14. Recommended Location of Ball Valves ● Select a valve location that allows service to be easily pr
22 - 25Design of Mini Multiset3. Installation Instructions3-2. Outdoor UnitAVOID:● heat sources, exhaust fans, etc. (Fig. 2-6)● damp, humid or uneve
22 - 26Design of Mini Multiset3. Installation InstructionsFig. 2-10Fig. 2-11Fig. 2-123-3. Air Discharge Chamber for Top DischargeBe sure to install
22 - 27Design of Mini Multiset3. Installation Instructions3-6. Dimensions of Air-Discharge ChamberReference diagram for air-discharge chamber (field
22 - 28Design of Mini Multiset3. Installation InstructionsMore than 2000More than 400More than 1500Installation with intakes facing outletsInstallati
22 - 29Design of Mini Multiset3. Installation Instructions4446452337323881209233021012337324612097641415045050020338500417307781695500Fastened by scr
22 - 30Design of Mini Multiset3. Installation InstructionsUnit: mmReference diagram for snow-proof vents – 1Space requirements for setting – (1)AES 0
22 - 31Design of Mini Multiset3. Installation InstructionsReference diagram for snow-proof vents – 2Space requirements for setting – (2)AES 04-05-06
22 - 32Design of Mini Multiset3. Installation Instructions3-10. Installing the Outdoor Unit● Use concrete or a similar material to create the base,a
ii2. The standards for minimum room volume are asfollows.(1) No partition (shaded portion)(2) When there is an effective opening with the adja-cent ro
22 - 33Design of Mini Multiset4. Electrical WiringControl wiring(C) Inter-unit (between outdoor and indoor units) control wiring(D) Remote control w
22 - 34Design of Mini Multiset4. Electrical Wiring4-3. Wiring System DiagramU2U131212NL1221WHTRemote controllerBLK21U2U131212U2U131212U2U13121221WHTRe
22 - 35Design of Mini MultisetOutdoor unitOutdoor unitOutdoor unitIndoor unit Indoor unit Indoor unit Indoor unitIndoor unitmore than 1 mmore than 1 m
22 - 36Design of Mini MultisetFig. 4-4Shielded wireGroundGroundFig. 4-5Stranded wireRingpressure terminalStrip 10 mmFig. 4-6WireSpecialwasherScrewRing
33 - 1Mini Multiset Unit SpecificationsContents3. Mini Multiset unit specifications1. Outdoor Unit 1-1. Specifications . . . . . . . . . . . . . .
33 - 3Mini Multiset Unit Specifications1. Outdoor Unit1-1. SpecificationsUnit specifications (A)MODEL No. Outdoor Unit AES 04 MMIHPOWER SOURCE 220 -
33- 4Mini Multiset Unit Specifications1. Outdoor UnitUnit specifications (B)MODEL No. Outdoor Unit AES 05 MMIHPOWER SOURCE 220 - 230 - 240 V / Single
33 - 5Mini Multiset Unit Specifications1. Outdoor UnitUnit specifications (C)MODEL No. Outdoor Unit AES 06 MMIHPOWER SOURCE 220 - 230 - 240 V / Singl
33 - 6Mini Multiset Unit Specifications1. Outdoor UnitUnit specifications (D)MODEL No. Outdoor Unit AES 04 MMIHPOWER SOURCE 220 - 230 - 240 V / Singl
3 3- 7Mini Multiset Unit Specifications1. Outdoor UnitUnit specifications (E)MODEL No. Outdoor Unit AES 05 MMIHPOWER SOURCE 220 - 230 - 240 V / Singl
iii Mini Multiset VRF DCI2. Design of Mini Multiset1. Model Selecting and Capacity Calculator . . . . . . . . . . . . . . . . . . . . .
33 - 8Mini Multiset Unit Specifications1. Outdoor UnitUnit specifications (F)MODEL No. Outdoor Unit AES 06 MMIHPOWER SOURCE 220 - 230 - 240 V / Singl
3 3- 9Mini Multiset Unit Specifications1. Outdoor UnitOutdoor unit (A)MODEL No. AES 04 MMIHPower source 220 - 230 - 240 V / 1N / 50 HzController P.C.
33- 10Mini Multiset Unit Specifications1. Outdoor UnitOutdoor unit (B)MODEL No. AES 05 MMIHPower source 220 - 230 - 240 V / 1N / 50 HzController P.C.
33 - 11Mini Multiset Unit Specifications1. Outdoor UnitOutdoor unit (C)MODEL No. AES 06 MMIHPower source 220 - 230 - 240 V / 1N / 50 HzController P.C
33 - 12Mini Multiset Unit Specifications1. Outdoor UnitOutdoor unit (D)MODEL No. AES 04 MMIHPower source 220 - 230 - 240 V / 1N / 50 HzController P.C
33 - 13Mini Multiset Unit Specifications1. Outdoor UnitOutdoor unit (E)MODEL No. AES 05 MMIHPower source 220 - 230 - 240 V / 1N / 50 HzController P.C
33 - 14Mini Multiset Unit Specifications1. Outdoor UnitOutdoor unit (F)MODEL No. AES 06 MMIHPower source 220 - 230 - 240 V / 1N / 50 HzController P.C
33- 15Mini Multiset Unit Specifications1. Outdoor Unit1-3. Dimensional DataAES 04 MMIH-AES 05 MMIH-AES 06 MMIHíËë¨ÉGÉXÉpédólíËë¨ÉGÉXÉpédól1703402962
33 - 16Mini Multiset Unit Specifications1. Outdoor Unit1-4. Refrigerant Flow DiagramHPSDischargeAES 04 MMIH 6AES 05 MMIHAES 06 MMIH SuctionHP
3 - 17Mini Multiset Unit Specifications31. Outdoor UnitNOTEModelSound PowerLevelConditionSound Power Level (dB)Frequency at center of sound pressure
11 - 1Outline of Mini MultisetContents1. Outiline of Mini Multiset1. Line-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 3- 18Mini Multiset Unit Specifications1. Outdoor UnitNOTEModelSound PowerLevelConditionSound Power Level (dB)AES 06 MMIH68 dB (A)Cooling10203040506
3 - 19Mini Multiset Unit Specifications3ModelSound Pressure LevelCoolingConditionOctave Band Level (dB)** 0 dB = 0.0002 ∝barFrequency at center of sou
33 - 20Mini Multiset Unit Specifications1. Outdoor UnitModelSound Pressure LevelCoolingConditionOctave Band Level (dB)** 0 dB = 0.0002 ∝barFrequency
4 - 14Test Run and OthersContents4. Test Run and Others1. Air Purging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 - 24Test Run and Others1. Air PurgingFig. 5-1Fig. 5-2Air and moisture in the refrigerant system may haveundesirable effects as indicated below. pre
4 - 34Test Run and Others1. Air Purging(3) Do a leak test of all joints of the tubing (bothindoor and outdoor) and both gas tube and liquidtube servic
4 - 44Test Run and Others1. Air PurgingFig. 5-5Fig. 5-6Charging additional refrigerant Charging additional refrigerant (calculated from theliquid tub
4- 54Test Run and Others2. Test Run2-1. Preparing for Test Run Before attempting to start the air conditioner,check the following.(1) All loose matt
4- 64Test Run and Others2. Test RunYESMake necessary corrections.Check the alarm contents.Check the alarm contents.Turn OFF the indoor and NO*2*3 *3*2
4-- 74Test Run and Others2. Test Run2-3. Outdoor Unit PCB SettingCN51CN50D043(LED2)D042(LED1)S003CN33S002S004Fig. 5-10
11 -2Outline of Mini Multiset1. Line-upOutdoor unitsTypeCapacity:kW (BTU/h)14.0 (47,800) 15.5 (52,900)Cooling /Heating/ 16.0 (54,600)11.2 (38,200) /
4 - 84Test Run and Others2. Test Run11121ON21ONON1221ON2109ONOFFONOFFONOFFONOFF Examples of refrigerant circuit (R.C.) address settings (required when
4- 94Test Run and Others2. Test Run2-4. Auto Address SettingBasic wiring diagram: Example (1)(S004)1-11-2 1-31-8• If link wiring is not used(The inte
4- 104Test Run and Others2. Test Run1-1 1-22-1 2-2 2-71-3 1-6277ON12ONOFFAutomatic address setting in Heating modeAutomatic address setting in Cooling
4- 114Test Run and Others2. Test RunAutomatic Address Setting (no compressor operation) Indoor and outdoor unit power can be turned ON for each syste
4- 124Test Run and Others2. Test RunAutomatic Address Setting in Heating Mode Indoor and outdoor unit power cannot be turned ON for each system separ
4- 134Test Run and Others2. Test RunAutomatic Address Setting in Cooling Mode Indoor and outdoor unit power cannot be turned ON for each system separ
4- 144Test Run and Others2. Test Runis blinkingLED 1 LED 2( : ON : Blinking : OFF)Display meaningAfter the power is turned ON (and automatic address
4- 154Test Run and Others2. Test RunRequest concerning recording the indoor/outdoor unit combination Nos. After automatic address setting has been com
4- 164Test Run and Others2. Test RunPossible cause of malfunctionRemote controller is detectingerror signal from indoor unit.Indoor unit is detecting
4- 174Test Run and Others2. Test RunThermistorfaultProtectivedevice forcompressor isactivatedIndoor thermistor is either openor damaged.Outdoor thermi
22 - 1Design of Mini Multiset2. Design of Mini Multiset1. Model Selecting and Capacity Calculator . . . . . . . . . . . . . . . . . . . . . . . . .
4- 184Test Run and Others3. Electrical WiringControl wiring(C) Inter-unit (between outdoor and indoor units) control wiring(D) Remote control wiring
4- 194Test Run and Others3. Electrical Wiring3-3. Wiring System DiagramU2U131212NL1221WHTRemote controllerBLK21U2U131212U2U131212U2U13121221WHTRemote
4- 204Test Run and Others3. Electrical WiringOutdoor unitOutdoor unitOutdoor unitIndoor unit Indoor unit Indoor unit Indoor unitIndoor unitmore than 1
4- 214Test Run and Others3. Electrical WiringFig. 5-16Shielded wireGroundGroundFig. 5-17Stranded wireRingpressure terminalStrip 10 mmFig. 5-18WireSpec
4- 224Test Run and Others4. Installation Standards2. The standards for minimum room volume are asfollows.(1) No partition (shaded portion)(2) When the
4- 234Test Run and Others4. Installation StandardsNewtool?(2) Prevent impurities including water, dust and oxide from entering the tubing. Impurities
4- 244Test Run and Others4. Installation StandardsValveLiquid(2) Use R410A exclusive cylinder only.Single-outlet valve(with siphon tube)Liquid refrige
Via Varese, 90 - 21013 Gallarate - Va - ItalyTel. +39 0331 755111 - Fax +39 0331 776240www.argoclima.com
22 - 2Design of Mini Multiset1. Model Selecting and Capacity Calculator1-1. Operating Range10–10–15–5051015202530354045Indoor air intake temp. °C (W