Argo AWR222CLE - AER222SC Wartungshandbuch

Stöbern Sie online oder laden Sie Wartungshandbuch nach Split-System-Klimaanlagen Argo AWR222CLE - AER222SC herunter. Argo AWR222CLE - AER222SC Service manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUALSPLIT SYSTEM AIR CONDITIONERAWR222CLE - AER222SCAWR222CLE - AER222SC30.8180.076.0 03/00

Seite 2 - Please Read Before Starting

2-3. Other Component SpecificationsIndoor Unit AWR222CLE7Outdoor Unit AER222SCOutdoor Unit AER222SC3Thermostat (Fan Speed Control 23S) YTB-S383Switchi

Seite 3 - Table of Contents

83. DIMENSIONAL DATAIndoor Unit AWR222CLEUnit : mm100036020574614964Rear panel (center point of gravity)Drain hose ø26Narrow tube ø6.35 (1/4")Wid

Seite 4 - 1. OPERATING RANGE

9Outdoor Unit AER222SCAER222SC3Unit : mmWide tube service valve ø15.88 (5/8")Narrow tube service valve ø6.35 (1/4")Check port ø6.35 (1/4&quo

Seite 5 - 2. SPECIFICATIONS

4. REFRIGERANT FLOW DIAGRAM10Indoor Unit AWR222CLE Outdoor Unit AER222SCAER222SC3CompressorAccumulatorWide tubeservicevalveWide tubeO.D.ø15.88 mm(5/8

Seite 6

5. PERFORMANCE DATA5-1. Performance charts11Indoor inlet airD.B. temp. (°C)Outdoor fan speedHighLow25 30 35 40 45 50Outdoor inlet air D.B. temp. (°C)

Seite 7 - 2-2-1. Indoor Unit

12Indoor inlet airD.B. temp. (°C)Outdoor fan speedHighLow25 30 35 40 45 50Outdoor inlet air D.B. temp. (°C) Cooling Characteristics98765432125 30 35

Seite 8 - 2-2-2. Outdoor Unit

135-2. Air Throw Distance ChartIndoor Unit AWR222CLE01234567891234Horizontal distance (m)Axis air verocity (m/s)Vertical distance (m)Axis air verocity

Seite 9

145-3. Cooling CapacityIndoor Unit AWR222CLEOutdoor Unit AER222SC240V Single Phase 50HzRATING CAPACITY 6.40 kWAIR FLOW RATE 900m3/hEVAPORATOR CONDEN

Seite 10 - Outdoor Unit AER222SC3

15Indoor Unit AWR222CLEOutdoor Unit AER222SC3240V Single Phase 50HzRATING CAPACITY 6.25 kWAIR FLOW RATE 900m3/hEVAPORATOR CONDENSERENT. TEMP. °C OU

Seite 11 - 3. DIMENSIONAL DATA

166. ELECTRICAL DATA6-1. Electrical CharacteristicsIndoor Unit Outdoor Unit Complete UnitFan Motor Fan Motor CompressorPerformance at 220V Single phas

Seite 12 - Air discharge

iImportant! Please Read Before StartingThis air conditioning system meets strict safety andoperating standards. As the installer or service person,it

Seite 13 - 4. REFRIGERANT FLOW DIAGRAM

176-2. Electric Wiring DiagramsTo avoid electrical shock hazard, be sure todisconnect power before checking, servicingand/or cleaning any electrical p

Seite 14 - 5. PERFORMANCE DATA

18To avoid electrical shock hazard, be sure todisconnect power before checking, servicingand/or cleaning any electrical parts.WARNINGOutdoor Unit AER2

Seite 15 - ■ Cooling Characteristics

19To avoid electrical shock hazard, be sure todisconnect power before checking, servicingand/or cleaning any electrical parts.WARNINGOutdoor Unit AER2

Seite 16 - 5-2. Air Throw Distance Chart

7. FUNCTION7-1. Room Temperature Control●Room temperature control is obtained by cycling the compressor ON and OFF under control of the roomtemperatur

Seite 17 - 5-3. Cooling Capacity

7-2. Freeze Prevention●This function prevents freezing of the indoor heat exchange coil.●When the compressor has been running for 10 minutes or more a

Seite 18 - 240V Single Phase 50Hz

7-3. Outdoor Fan Speed Control●To optimize performance of the air conditioner, the outdoor fan speed is switched automatically according to theoutdoor

Seite 19 - 6. ELECTRICAL DATA

8. TROUBLESHOOTING8-1. Check before and after troubleshooting8-1-1. Check power supply wiring.● (For model AER222SC)Check that power supply wires are

Seite 20 - 6-2. Electric Wiring Diagrams

8-2. Air conditioner does not operate.8-2-1. Circuit breaker trips (or fuse blows).A. When the circuit breaker is set to ON, it is tripped soon. (Res

Seite 21

B. Circuit breaker trips in several minutes after turning the air conditioner on.●There is a possibility of short circuit.Replace with suitableone (l

Seite 22

8-2-2. Neither indoor nor outdoor unit runs.A. Power is not supplied.B. Check remote control unit.C. Check "OPERATION selector" switch in th

Seite 23 - 7. FUNCTION

Table of ContentsPage1. OPERATING RANGE ...

Seite 24 - 7-2. Freeze Prevention

D. Check transformer in indoor unit.E. Check fuse on the indoor PCB Ass'y.F. Check TIMER SELECT button on the remote control unit.•Timer is turne

Seite 25

8-2-3. Only outdoor unit does not run.A. Check setting temperature.B. Check relay in outdoor unit. (AER222SC3)OK•Measure coil resistance of relay.Chec

Seite 26 - 8. TROUBLESHOOTING

C. Check negative phase relay. (Only for 3-phase model)D. Check magnetic contactor.E. Check indoor PCB Ass'y.F. Check compressor motor protector.

Seite 27

8-3. Some part of air conditioner does not operate.8-3-1. Only indoor fan does not run.8-3-2. Only outdoor fan does not run.Fan cannotbe turned.OK•Che

Seite 28

8-3-3. Only compressor does not run.8-3-4. Only louver motor does not run.8-3-5. Function of outdoor fan speed control does not work properly.• Check

Seite 29 - B. Check remote control unit

8-4. Air conditioner operates, but abnormalities are observed.8-4-1. Poor cooling.8-4-2. Excessive cooling.NONO•Set temperature is suitable.Set temper

Seite 30

8-5. If a sensor is defective.8-5-1. Indoor coil temp. thermistor (TH1) is defective.A. OpenWhen thermistor opens, the air conditioner will be in the

Seite 31 - A. Check setting temperature

9. REFRIGERANT R407C : SPECIAL PRECAUTIONS WHEN SERVICING UNIT9-1. Characteristics of new refrigerant R407C9-1-1.What is new refrigerant R407CR407C is

Seite 32 - (Only for 3-phase model)

9-3. Tools specifically for R407C● For servicing, use the following tools for R407C ● The above tools specifically for R407C must not be used for R22

Seite 33

9-5. In case of compressor malfunction● Should the compressor malfunction, be sure to replace compressor as quickly aspossible. ● Use only the tools i

Seite 34

11. OPERATING RANGETemperature Indoor Air Intake Temp. Outdoor Air Intake Temp.CoolingMaximum 32°C D.B. / 23°C W.B. 43°C D.B.Minimum 19°C D.B. / 14°C

Seite 35 - 8-4-2. Excessive cooling

ValveValveSingle valveCharge the liquid refrigerant with the cylinder in the up-side-down position.Single valve (with siphon tube)Charge with the cyli

Seite 36 - Thermistor Structure

9-6. In case refrigerant is leaking● Never attempt to charge additional refrigerant when refrigerant has been leakingfrom the unit. Follow the procedu

Seite 37 - 9. REFRIGERANT R407C :

(6) Recharging• Be sure to charge the specified amount ofrefrigerant in liquid stateusing the service port ofwide tube service valve. The proper amoun

Seite 38

9-7. Charging additional refrigerant9-7-1.When tubes are extended• Observe the proper amount of refrigerant as stated in this service manual or the in

Seite 39 - Standard time of evacuation

4510-1.Measurement of InsulationResistance●The insulation is in good condition if the resistanceexceeds 2MΩ.10-1-1. Power Supply WiresClamp the ground

Seite 40

4610-2.Checking Continuity of Fuse onPCB Ass'y●Remove the PCB Ass’y from the electricalcomponent box. Then pull out the fuse from the PCBAss’y. (

Seite 41

FILIBERTIS.p.A.*DOODUDWH9$9LD9DUHVH,WDO\7HO)D[(PDLOLWDOLD#DUJRFOLPDFRP

Seite 42

2. SPECIFICATIONS2-1. Unit SpecificationsDATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Indoor air temperature 27°C DB/19°C WBOu

Seite 43 - 9-8-2 Use of existing tubing

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Indoor air temperature 27°C DB/19°C WBOutdoor air temperature 35°C DB/24°C WB3Pow

Seite 44 - Resistance

2-1. Major Component Specifications2-2-1. Indoor UnitDATA SUBJECT TO CHANGE WITHOUT NOTICE.Source 220 – 240 V ~50 HzPart No. POW-K185GS-NControls Micr

Seite 45 - 10-3.Checking Motor Capacitor

2-2-2. Outdoor UnitDATA SUBJECT TO CHANGE WITHOUT NOTICE.Type Rotary (Hermetic)Compressor model C-RN221H5A 80244035Source 220 – 240 V ~50 HzNominal

Seite 46 - FILIBERTIS.p.A

DATA SUBJECT TO CHANGE WITHOUT NOTICE.Power source 380 – 400 V – 3N ~50 HzControl circuit 220 – 240 V ~50 HzType Rotary (Hermetic)Compressor model C-